dc.description.abstract | RESUMEN : En el presente informe se planea conectar un proyecto fotovoltaico de 60 MW al SIN. Para la conexión del proyecto solar se analizaron 2 alternativas en el horizonte 2025 y 2030: Alternativa 1: Conexión de la planta a la Subestación 1 en 115 kV, mediante un circuito sencillo de 5,35 km. Alternativa 2: Conexión de la planta a la Subestación 2 en 115 kV, mediante un circuito sencillo de 79,25 km. Para las alternativas de conexión planteadas, se realizan simulaciones de flujo de carga, cortocircuito, estabilidad dinámica, transitoria y evaluación económica. Los resultados obtenidos del flujo de carga muestran que la conexión del parque solar al SIN presenta un buen desempeño técnico mediante cualquiera de las alternativas de conexión en los dos años de estudio para todos los escenarios evaluados, en condiciones normales de operación. Por otra parte, de los análisis de contingencias N-1, se encuentra que ante la salida de los elementos Transformador A, Línea A y Línea C, se generan sobrecargas tanto en el Caso Base como en la conexión de la Alternativa 1 y la Alternativa 2. La condición evidenciada es propia de la red y asociada a las condiciones de demanda esperadas en el sistema. Los análisis técnicos de cortocircuito y estabilidad muestran que, con el ingreso de la planta mediante cualquiera de las alternativas analizadas, y ante la ocurrencia de cualquiera de los eventos simulados, el sistema presenta un comportamiento adecuado, manteniendo sus variables dentro de rangos aceptables, tanto en estado estable como transitorio. Los resultados de la evaluación económica muestran que la Alternativa 1 es mejor que la Alternativa 2, ya que tiene una relación B/C mayor y los costos de inversión son menores. | spa |
dc.description.abstract | ABSTRACT : This report studies the connection of a 60 MW PV Project to the SIN (Sistema Interconectado Nacional). For the connection of the solar project, two alternatives are analyzed in the horizon of 2025 and 2030. Alternative 1: Connection of the plant to the Substation 1 in 115 kV, through a simple circuit of 5,35 km. Alternative 2: Connection of the plant to the Substation 2 in 115 kV, through a simple circuit of 79,25 km. For the proposed alternatives, simulations like load flow, shortcircuit, dynamic and transient stability, and economic evaluation are performed. The results obtained from the load flow shows that the connection of the solar park to the SIN presents a good technical performance in the two years of study and for all the scenaries evaluated, under normal operating conditions. On the other hand, from the N-1 contigencies analysis, it can be seen that after the outage of the Transformer A, Line A and Line C, overloads are generated both in the base case and with the connection of Alternative 1 and Alternative 2. This condition is associated to the load conditions expected in the system. The technical analysis of shortcircuit and stability, show that with the entrance of the PV plant through any alternative, and during the ocurrence of any of the simulated events, the system presents an adequate behavior, keeping its variables within aceptable ranges, both in a stable and transient state. The economic evaluation results show that the Alternative 1 is better than the Alternative 2, because it has a higher B/C ratio and the investment costs are lower. | spa |
dc.format.extent | 57 | spa |
dc.format.mimetype | application/pdf | spa |
dc.language.iso | spa | spa |
dc.type.hasversion | info:eu-repo/semantics/draft | spa |
dc.rights | info:eu-repo/semantics/openAccess | spa |
dc.rights.uri | http://creativecommons.org/licenses/by-nc-sa/2.5/co/ | * |
dc.title | Apoyo en la elaboración de estudios de conexión: Estudio de conexión de Parque Solar de 60 MW | spa |
dc.type | info:eu-repo/semantics/bachelorThesis | spa |
oaire.version | http://purl.org/coar/version/c_b1a7d7d4d402bcce | spa |
dc.rights.accessrights | http://purl.org/coar/access_right/c_abf2 | spa |
thesis.degree.name | Ingeniero Electricista | spa |
thesis.degree.level | Pregrado | spa |
thesis.degree.discipline | Facultad de Ingeniería. Ingeniería Eléctrica | spa |
thesis.degree.grantor | Universidad de Antioquia | spa |
dc.rights.creativecommons | https://creativecommons.org/licenses/by-nc-sa/4.0/ | spa |
dc.publisher.place | Medellín - Colombia | spa |
dc.type.coar | http://purl.org/coar/resource_type/c_7a1f | spa |
dc.type.redcol | https://purl.org/redcol/resource_type/TP | spa |
dc.type.local | Tesis/Trabajo de grado - Monografía - Pregrado | spa |
dc.subject.lemb | Circuitos eléctricos | - |
dc.subject.lemb | Cortocircuitos | - |
dc.subject.lemb | Costos marginales | - |
dc.subject.lemb | Sistemas eléctricos | - |
dc.subject.spines | Análisis económico | - |
dc.subject.spines | Generación de energía eléctrica | - |
dc.subject.spines | Potencia (eléctrica) | - |
dc.subject.proposal | Flujo de potencia | spa |
dc.subject.proposal | Parque solar | spa |